 DC Current transducer DK-B5/10
A split core transducer for the electronic measurement DC current, with galvanic isolation between the primary (High power) and the secondary circuits (Electronic circuit) with voltage output.
IPN = 50..400A
Electrical data
Primary Nominal Current IPN (A.t) 50,75,100 100,150,200 150,225,300 200,300,400 50,75,100 100,150,200 150,225,300 200,300,400 Vc RL Vd f Ic Supply voltage Load resistance (max) Isolation voltage Frequency Current consumption (max) Analogue Output Signal 1) VOUT (V) 0-5 0-5 0-5 0-5 0-10 0-10 0-10 0-10 22-26 250 3000 DC 100 Type
Features
* DC Measurement * Split core box * Voltage output * Jumper selectable ranges * Panel mounting * Extended measuring range
DK 100 B5 DK 200 B5 DK 300 B5 DK 400 B5 DK 100 B10 DK 200 B10 DK 300 B10 DK 400 B10 V AC/ DC k V AC mA
Advantages
* Large aperture * High isolation between primary and secondary circuits * Easy to mount * No insertion losses
Applications
* Battery Banks - Monitors load current. - Monitors charging current. - Verifies operation. * Transportation Measures traction power or auxiliary loads. * Electric Heating Elements Faster response than temperature sensors.
Accuracy - Dynamic performance data
X L tr Accuracy @ IPN, TA=25C Linearity Response time @ 90% of I PN 1 0.75 < 300 % % mS
General data
TA TS m Ambient operating temperature (0-95% RH) Ambient storage temperature Mass - 20 .. + 50 - 20 .. + 85 120 C C g
Options on request
* DIN mounting
Note :
1)
For 0-3 V output model, no saturation output up to 3.5 V for 0-5 V output model, no saturation output up to 5.75 V and for 0-10 V output model, no saturation output up to 11.5 V
040405/5 w w w .lem.com
LEM Components
Dimensions
DK-B5/10
(unit : mm, 1mm = 0.0394 inch)
61
21.7
13
57.2
3.2
13
21.7 89.7 61
30
4.5
77.3
Mechanical characteristics
* General tolerance * Primary aperture * Panel mounting Distance between holes 1 mm 21.7 mm sq. 2 holes 4.5mm 77.3 mm
Output
output in %
100
- IP
+ IP
Connections
* 2 x UNC8 Cylindric Head
22-38 VAC 22-26 VAC/DC
Range Jumper
1(-) 2(+) 3(-) 4(+) Output Power
- Dead front captive screw terminals - 12-22AWG solid or stranded
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.


▲Up To Search▲   

 
Price & Availability of DK400-B10

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X