 SRC
DEVICES
TWO ELECTRODE HIGH VOLTAGE SURGE ARRESTERS 2 ELECTRODE HIGH VOLTAGE SURGE ARRESTERS CG3 Series
DESCRIPTION
SRC Devices 2 electrode high voltage CG3 Comgaps (1.0 - 8.5 kV) are designed for surge protection in applications for which bias voltages or signal levels of several hundred volts are normally present. Comgaps function as switches which dissipate a minimum amount of energy and therefore handle currents that far surpass other types of transient voltage protection.
FEATURES
s s s s s
APPLICATIONS
s s s s s
Rugged ceramic-metal construction Non-radioactive Low capacitance (<1pF) Available in tape-and-reel packaging Available with or without leads
CRT terminal CATV equipment Antennas Power supplies Medical electronics
APPROVALS
s UL Recognized: File Number E111526 s CSA Approved: File Number LR89617
Parameter
RATINGS (@ 25o C)
Min 800 1200 1600 2000 2400 3200 4000 6000 6800 1010 -40 Typ 1000 1500 2000 2500 3000 4000 5000 7500 8500 Max 1200 1800 2400 3000 3600 4800 6000 9000 10200 1 +125 Unit V V V V V V V V V pF C
DC Breakdown Voltage
Insulation Resistance Capacitance Operational Temperature
(See detailed specifications for more information.)
USA 1-866-SRC-8668 Europe 32-89-328850
Far East 886-2-2698-8422
www.srcdevices.com
8
TWO ELECTRODE HIGH VOLTAGE SURGE ARRESTERS CG3 Series
SPECIFICATIONS
CG3-1.0 All characteristics at 25 C
o
SRC
CG3-1.5 CG3-1.5L
DEVICES
CG3-1.0L
PARAMETER Device Specifications DC Breakdown Impulse Breakdown Insulation Resistance Capacitance Arc Voltage Mechanical Outline Life Ratings(1) Surge Life Max Current Surge AC Follow-on Current
CONDITIONS 500V/s 100V/s 100V 1MHz I=5A min
SYMBOL VBD VBD IR C VARC -
MIN 800 1010 500 5 -
TYP 1000 10 A -
MAX 1200 1500 1 300
MIN 1200 1010 500 5 -
TYP 1500 10 A -
MAX 1800 2200 1 300
UNITS V V
pF V shots shots A pk
1
.002mF, 100 10kA (8/20s) /2 cycle @ 60Hz
CG3-2.0 CG3-2.0L
PARAMETER Device Specifications DC Breakdown Impulse Breakdown Insulation Resistance Capacitance Arc Voltage Mechanical Outline Life Ratings(1) Surge Life Max Current Surge AC Follow-on Current CONDITIONS 500V/s 100V/s 100V 1MHz I=5A min SYMBOL VBD VBD IR C VARC MIN 1600 1010 500 5 TYP 2000 10 A MAX 2400 3000 1 300
CG3-2.5 CG3-2.5L
MIN 2000 1010 500 5 TYP 2500 10 A MAX 3000 3750 1 300 UNITS V V
pF V shots shots A pk
.002mF, 100 10kA (8/20s) 1 /2 cycle @ 60Hz
CG3-3.0 CG3-3.0L
PARAMETER Device Specifications DC Breakdown Impulse Breakdown Insulation Resistance Capacitance Arc Voltage Mechanical Outline Life Ratings(1) Surge Life Max Current Surge AC Follow-on Current CONDITIONS 500V/s 100V/s 100V 1MHz I=5A min SYMBOL VBD VBD IR C VARC MIN 2400 1010 500 5 TYP 3000 10 B MAX 3600 4500 1 300
CG3-4.0 CG3-4.0L
MIN 3200 1010 500 5 TYP 4000 10 B MAX 4800 6000 1 300 UNITS V V
pF V shots shots A pk
.002mF,100W 10kA (8/20s) 1 /2 cycle @ 60Hz
(1)End-of-life limits are: DC: 50% of minimum initial DC breakdown voltage limit to 150% of maximum initial DC breakdown voltage limit. Impulse: less than 150% of initial impulse breakdown voltage limit.
USA 1-866-SRC-8668 Europe 32-89-328850
Far East 886-2-2698-8422
www.srcdevices.com
9
SRC
DEVICES TWO ELECTRODE HIGH VOLTAGE SURGE ARRESTERS CG3 Series
SPECIFICATIONS
CG3-5.0 All characteristics at 25C CG3-5.0L CG3-7.5 CG3-7.5L CG3-8.5 CG3-8.5L
PARAMETER Device Specifications
DC Breakdown Impulse Breakdown Insulation Resistance Capacitance Arc Voltage Mechanical Outline
CONDITIONS
500V/s 100V/s 100V 1MHz I=5A min
SYMBOL MIN TYP
VBD VBD IR C VARC -
MAX
MIN
6000 1010 500 5 -
TYP
MAX
MIN
TYP
MAX UNITS
V V
4000 5000 6000 7500 1010 1 10 B 500 5 300
7500 9000 6800 10000 1010 1 10 B 300 500 5 -
8500 10200 13500 1 10 B 300
pF V shots shots A pk
Life Ratings(1)
Surge Life Max Current Surge AC Follow-on Current .002mF,100 10kA (8/20s) 1 /2 cycle @ 60Hz
(1)End-of-life limits are: DC: 50% of minimum initial DC breakdown voltage limit to 150% of maximum initial DC breakdown voltage limit. Impulse: less than 150% of initial impulse breakdown voltage limit.
MECHANICAL DIMENSIONS
Other lead forms are available upon request. Contact SRC Devices for more information.
Outline A
ORDERING INFORMATION
CG3's with other breakdown voltages in the 1.0-8.5kV range are available upon request. A complete part number is represented by the digits below. For example, CG3-1.5 is a non-leaded 1500V device, CG3-5.0L is a leaded 5000V device, and CG3-7.5LTR is a leaded 7500V device on tape-and-reel per EIA standard RS-296-D.
DIMENSIONS mm (inches)
56.15 1.25 (2.210 0.050)
CG3 X.X X XX
Series
CG3
0.81 DIA. TYP. (0.032)
Shipping Package
TR = Tape & Reel (Blank) = Bulk
3.56 9.14 DIA.MAX. (0.140) (0.360)
Breakdown Voltage
1.0 = 1000V 1.5 = 1500V 2.0 = 2000V 2.5 = 2500V 3.0 = 3000V 4.0 = 4000V 5.0 = 5000V 7.5 = 7500V 8.5 = 8500V
Options
L = Leads (Blank) = No Leads
7.57 0.19 (0.298 0.008)
Outline B
Tape & Reel Information
58.67 1.25 (2.310 0.050)
9.14 DIA.MAX. (0.360)
0.81 DIA. TYP. (0.032)
CG3XXLTR - Tape & Reel per EIA RS-296-D. Quantity = 1,000/Reel CG3XXLTE - Tape & Reel per IEC286-1. Quantity = 1,000/Reel
3.56 (0.140)
10.11 0.19 (0.398 0.008)
USA 1-866-SRC-8668 Europe 32-89-328850
Far East 886-2-2698-8422
www.srcdevices.com
10


▲Up To Search▲   

 
Price & Availability of CG3

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X