Part Number Hot Search : 
IWR0520F LTC3828 1V330M JS28F256 AN5109B 2SC6097 STA328 IR211
Product Description
Full Text Search
 

To Download MDL Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Sync*CircuitTM Module
The Sync*Circuit module synchronizes SpectrAlert(R) Advance strobes at 1 Hz and horns and chimes at temporal 3 over a single pair of wires. Patented module technology also allows the silencing of horns or chimes on horn/strobe and chime/strobe models over a pair of wires.
Features
* Two-wire operation from module to the devices * Silences horns and chimes over a two-wire loop * Synchronizes strobes at 1 Hz * Synchronizes horns and chimes to temporal 3 pattern * Patented technology * Allows slave module operation
The MDL Module is designed to work with the SpectrAlert and SpectrAlert Advance series of notification appliances to provide a means of synchronizing the temporal-coded horns and chimes, synchronizing the one-second flash timing of the strobe, and silencing the horns and chimes of the horn/strobe and chime/ strobes combination over a two-wire circuit while leaving the strobes active. Application Flexibility. The Sync*Circuit module is designed to power and synchronize either two 3-amp circuits wired in Class B, or one 3-amp circuit powered as Class A. Should more than two zones require synchronization, additional modules can be added by interconnecting the "slave" input and output terminals between modules.
Agency Listings
S5512 S4011
CS548/549
7300-1209:179
0D4A7.AY
254-97-M
Sync*CircuitTM Module Specifications
Architectural/Engineering Specifications Synchronization Circuit Module shall be a System Sensor Sync*Circuit Model _________ listed to UL464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert(R) strobes at 1 Hz and horns at temporal 3. Also, the module shall be capable of silencing the horns on horn/strobe models, while operating the strobes, over a single pair of wires. The module shall be capable of mounting to a 41116x 41116x 218 back box and shall control two Style Y (class B) or one Style Z (class A) circuit. The module shall be capable of multiple zone synchronization by connecting multiple modules together via a slave-in/ slave-out arrangement and re-synchronizing each other along the chain. Note: The module shall not operate on a coded power supply. Physical Specifications Dimensions 514 L x 514 W Mounting 41116 x 41116 x 218 back box Indoor Operating Temperature 32 to 120 F (0 to 49 C) Electrical/Operating Specifications Operating Voltage 12 or 24 VDC and FWR unfiltered Operating Voltage Range (12 V) 9 to 17.5 VDC Operating Voltage Range (24 V) 17 to 33 VDC Maximum Load on Loop 3 Amps/zone HORNS U.S. Patent Nos. 5,598,139 SILENCED OVER TWO WIRE CIRCUIT MASTER MODULE HORN CONTROL CONNECTS 5,850,178 TO INTERRUPTABLE POWER SOURCE
Horns and Chimes Silenced Over Two-Wire Circuit
1. Any mix of Horn/Strobes, Chime/Strobes or Strobe only devices is acceptable 2. Horn and chime control connects to interruptible power source
MASTER MODULE FACP #1 NAC1 SLAVE MODULE
(+) (-)
EOL
(+) (-)
NAC2
(+) (-)
(+) (-)
NAC3
(+) (-)
(+) (-)
(+) (-)
} } } }
HORN CONTROL
ZONE 1 OUT
ZONE 1 IN
ZONE 2 OUT
ZONE 2 IN
SYNC ERROR
SLAVE IN
SLAVE OUT
} } } }
FACP #2 TO NEXT SPECTRALERT DEVICE OR EOL
)+( )-(
)+( )-(
)+( )-(
NAC1
(+) (-)
(+) (-)
)+( )-(
)+( )-(
TO NEXT SPECTRALERT DEVICE OR EOL
NAC2
(+) (-)
(+) (-)
(+) (-)
} } } }
HORN CONTROL
ZONE 1 OUT
ZONE 1 IN
ZONE 2 OUT
ZONE 2 IN
SYNC ERROR
SLAVE IN
SLAVE OUT
} } } }
)+( )-(
)+( )-(
TO NEXT SPECTRALERT DEVICE OR EOL
)+( )-(
)+( )-(
TO NEXT SPECTRALERT DEVICE OR EOL
TEMP JUMPER OFF
TEMP JUMPER OFF
All SpectrAlert horns, horn/strobes, and strobes will operate in sync.
Current Draw and Ordering Information
Red MDL, MDLA (Canadian) White MDLW, MDLWA (Canadian) Voltage 12 24 Average Current (mA) DC FWR 10 12 11 15 Peak Current (mA) DC FWR 30 31 35 37 In-rush Current (mA) DC FWR 87 122 198 262
3825 Ohio Avenue * St. Charles, IL 60174 Phone: 800-SENSOR2 * Fax: 630-377-6495
(c)2007 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-1007-005 * 6/07 * #1676


▲Up To Search▲   

 
Price & Availability of MDL

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X