 Basic-type Digital Temperature Controller
E5AN/E5EN
(96 x 96 mm and 48 x 96 mm)
CSM_E5AN_E5EN_DS_E_3_2
New 96 x 96-mm and 48 x 96-mm Basic Temperature Controllers with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function.
* Indication Accuracy Thermocouple input: 0.3% of PV (previous models: 0.5%) Pt input: 0.2% of PV (previous models: 0.5%) Analog input: 0.2% FS (previous models: 0.5%) * A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV. * Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter. * Three-level display that simultaneously displays the PV, SV, and MV. * One-touch operation with PF Key that can be assigned to auto/ manual, RUN/STOP, or other functions.
96 x 96 mm E5AN
48 x 96 mm E5EN
Refer to Safety Precautions for E5@N/E5@N-H. Refer to Operation for E5@N/E5@N-H for operating procedures.
Main I/O Functions
E5AN
Event Inputs * None * Two Sensor Inputs * Universal thermocouple/Pt inputs (Models with temperature inputs) * Analog current/voltage inputs (Models with analog inputs) Indication Accuracy * Thermocouple input: 0.3% of PV * Pt input: 0.2% of PV * Analog input: 0.2% FS Sampling Period * 250 ms PF Key (Programmable function key) Control Output 2 * Voltage output (for driving SSR) * Long-life relay output (hybrid)
E5EN
3-level Display * Simultaneously displays set items, such as the PV, SV, and MV.
* A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level, refer to the User's Manual, Basic Type (Cat. No. H156).
4-digit Display * Auto/manual switching * Temperature Controller status display * Simple program function * Control output ON/OFF count alarm * PV change rate alarm * Models also available with RS-485 or RS-232C communications
Auxiliary Outputs * Three
Control Output 1 * Relay output * Voltage output (for driving SSR) * Current output
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)
1
E5AN/E5EN
Lineup
1 control output Temperature input 2 control outputs
3 auxiliary outputs 3 auxiliary outputs
E5AN/E5EN Basic Type
Terminal block 1 control output Analog input 2 control outputs
3 auxiliary outputs 3 auxiliary outputs
Note: Models with one control output or two control outputs can be used for heating/cooling control.
Model Number Structure
Model Number Legend
Controllers Option Units
E5AN/E5EN-@3@M@@-@-500-N
123 4 5 6
1. Control Output 1 R: Relay output Q: Voltage output (for driving SSR) C: Current output 2. Auxiliary Outputs 3: Three outputs 3. Heater Burnout/SSR Failure, Control Output 2, or External Power Supply for ES1B Blank: None Q: Control output 2 (voltage output for driving SSR) Y: Long-life relay output (hybrid) H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) P: Power supply for sensor 4. Option M: Option Unit can be mounted. 5. Input Type T: Universal thermocouple/platinum resistance thermometer input L: Analog current/voltage input 6. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 7. Case Color Blank: Black W: Silver 8. Terminal Cover -500: With terminal cover 9. Version N: Available only to models released after January 2008.
E53-@
1
1. Function EN01: RS-232C communications EN03: RS-485 communications AKB: Event input
7
8
9
2
E5AN/E5EN
Ordering Information
E5AN Controllers with Terminal Blocks
Size Case color Power supply voltage Input type Auxiliary Control output 1 outputs Relay output Voltage output (for driving SSR) Current output Relay output 1 Voltage output 1 (for driving SSR) Relay output 2 Voltage output 2 (for driving SSR) Thermocouple or Resistance thermometer 3 Relay output Voltage output (for driving SSR) Current output 100 to 240 VAC Relay output Voltage output (for driving SSR) Current output Relay output Black Voltage output (for driving SSR) Relay output Voltage output (for driving SSR) 1/4 DIN 96 x 96 x 78 (W x H x D) Current output Analog (current/voltage) 3 Relay output 1 Voltage output 1 (for driving SSR) Voltage output (for driving SSR) Relay output Voltage output (for driving SSR) 24 VAC/ VDC Thermocouple or Resistance thermometer Current output 3 Relay output 1 Voltage output 1 (for driving SSR) Relay output 2 Voltage output 2 (for driving SSR) Relay output Voltage output (for driving SSR) 100 to 240 VAC Silver Current output Thermocouple or Resistance thermometer Relay output 3 1 Voltage output 1 (for driving SSR) Relay output 24 VAC/ VDC Voltage output (for driving SSR) Sensor Power Sensor Power Voltage output Voltage output Voltage output Functions Heater Power supply Control burnout for Sensor output 2 Model E5AN-R3MT-500-N E5AN-Q3MT-500-N E5AN-C3MT-500-N E5AN-R3HMT-500-N E5AN-Q3HMT-500-N E5AN-R3HHMT-500-N E5AN-Q3HHMT-500-N E5AN-R3QMT-500-N E5AN-Q3QMT-500-N E5AN-C3QMT-500-N
E5AN-R3YMT-500-N Long-life relay E5AN-Q3YMT-500-N output E5AN-C3YMT-500-N E5AN-R3PMT-500-N E5AN-Q3PMT-500-N E5AN-R3ML-500-N E5AN-Q3ML-500-N E5AN-C3ML-500-N E5AN-R3HML-500-N E5AN-Q3HML-500-N Long-life relay E5AN-Q3YML-500-N output E5AN-R3MTD-500-N E5AN-Q3MTD-500-N E5AN-C3MTD-500-N E5AN-R3HMTD-500-N E5AN-Q3HMTD-500-N E5AN-R3HHMTD-500-N E5AN-Q3HHMTD-500-N E5AN-R3MT-W-500-N E5AN-Q3MT-W-500-N E5AN-C3MT-W-500-N E5AN-R3HMT-W-500-N E5AN-Q3HMT-W-500-N E5AN-R3MTD-W-500-N E5AN-Q3MTD-W-500-N E5AN-C3MTD-W-500-N
Current output Note: Models with analog inputs do not have temperature unit indicators.
3
E5AN/E5EN
E5EN Controllers with Terminal Blocks
Size Case color Power supply voltage Input type Auxiliary Control output 1 outputs Relay output Voltage output (for driving SSR) Current output Relay output 1 Voltage output 1 (for driving SSR) Relay output 2 Voltage output 2 (for driving SSR) Thermocouple or Resistance thermometer Relay output 3 Voltage output (for driving SSR) Current output 100 to 240 VAC Relay output Voltage output (for driving SSR) Current output Black Relay output Voltage output (for driving SSR) Relay output 1/8 DIN 48 x 96 x 78 (W x H x D) Voltage output (for driving SSR) Analog 3 (current/voltage) Current output Relay output Voltage output (for driving SSR) Relay output Voltage output (for driving SSR) 24 VAC/ VDC Thermocouple or Resistance thermometer Current output 3 Relay output 1 Voltage output 1 (for driving SSR) Relay output 2 Voltage output 2 (for driving SSR) Relay output 100 to 240 VAC Thermocouple or Resistance thermometer 24 VAC/ VDC Voltage output (for driving SSR) Current output Relay output 3 1 Voltage output 1 (for driving SSR) Relay output Voltage output (for driving SSR) 1 1 Sensor Power Sensor Power Voltage output Voltage output Voltage output Functions Heater Power supply burnout for Sensor Control output 2 Model E5EN-R3MT-500-N E5EN-Q3MT-500-N E5EN-C3MT-500-N E5EN-R3HMT-500-N E5EN-Q3HMT-500-N E5EN-R3HHMT-500-N E5EN-Q3HHMT-500-N E5EN-R3QMT-500-N E5EN-Q3QMT-500-N E5EN-C3QMT-500-N
Long-life E5EN-R3YMT-500-N relay output Long-life E5EN-Q3YMT-500-N relay output Long-life E5EN-C3YMT-500-N relay output E5EN-R3PMT-500-N E5EN-Q3PMT-500-N E5EN-R3ML-500-N E5EN-Q3ML-500-N E5EN-C3ML-500-N E5EN-R3HML-500-N E5EN-Q3HML-500-N Long-life E5EN-Q3YML-500-N relay output E5EN-R3MTD-500-N E5EN-Q3MTD-500-N E5EN-C3MTD-500-N E5EN-R3HMTD-500-N E5EN-Q3HMTD-500-N E5EN-R3HHMTD-500-N E5EN-Q3HHMTD-500-N E5EN-R3MT-W-500-N E5EN-Q3MT-W-500-N E5EN-C3MT-W-500-N E5EN-R3HMT-W-500-N E5EN-Q3HMT-W-500-N E5EN-R3MTD-W-500-N E5EN-Q3MTD-W-500-N E5EN-C3MTD-W-500-N
Silver
Current output Note: Models with analog inputs do not have temperature unit indicators.
4
E5AN/E5EN
Option Units
Name Communications Unit Event Input Unit Function RS-232C communications RS-485 communications Event inputs Model E53-EN01 E53-EN03 E53-AKB
Accessories (Order Separately)
USB-Serial Conversion Cable
Model E58-CIFQ1
Current Transformers (CTs)
Hole diameter 5.8 dia. 12.0 dia. Model Model E54-CT1 E54-CT3
Terminal Cover
Connectable models E5AN E53-COV16 E5EN Note: The Terminal Cover comes with the E5CN-@@@-500 models.
CX-Thermo Support Software
Model EST2-2C-MV4
Waterproof Packing
Connectable models E5AN Model Y92S-P4
E5EN Y92S-P5 Note: The Waterproof Packing is included with the Controller.
5
E5AN/E5EN
Specifications
Ratings
Power supply voltage Operating voltage range Power consumption No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC 85% to 110% of rated supply voltage 100 to 240 VAC: 10 VA 24 VAC/VDC: 5.5 VA (24 VAC)/4 W (24 VDC) Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor: 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C Voltage input: 0 to 50 mV Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Control method Relay output Voltage output (for driving SSR) Current output Long-life relay output Number of outputs Auxiliary Output output specifications Number of inputs Event input External contact input specifications Current input: 150 max., Voltage input: 1 M min. (Use a 1:1 connection when connecting the ES2-HB.) ON/OFF control or 2-PID control (with auto-tuning) SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Output voltage: 12 VDC 15% (PNP), max. load current: 40 mA, With short-circuit protection circuit: Max. load current of 21 mA for control output 2 4 to 20 mA DC/0 to 20 mA DC, load: 600 max., resolution: approx. 10,000 SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA max. (250 VAC, 60 Hz) 3 Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA 2 Contact input: ON: 1 k max., OFF: 100 k min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact External power supply for ES1B 12 VDC 10%, 20 mA, short-circuit protection circuit provided Setting method Digital setting using front panel keys 11-segment digital display and individual indicators (7-segments displays also possible) Character height: E5AN: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm Content of 3-level display: PV/SV/MV, PV/SV/multi-SP, or soak time remain * Number of digits: 4 for PV, SV, and MV Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial communications. Not supported. Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple program, automatic cooling coefficient adjustment 25% to 85%
Sensor input
Control output
Indication method
Multi SP Bank switching Other functions
Ambient operating temperature -10 to 55C (with no condensation or icing), for 3-year warranty: -10 to 50C Ambient operating humidity Storage temperature -25 to 65C (with no condensation or icing) * A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level, refer to the User's Manual, Basic Type (Cat. No. H156).
6
E5AN/E5EN
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Input type Name
2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 -100.0 -200.0 -200 -199.9 100.0 0.0 -199.9 100.0 100 0.0 -20.0 -100 -20.0 -200 -200 -199.9 -200 -100 -200 -199.9 -200 0 0 0 0 0 0 0 0 90 500.0 500.0 500.0 400.0 400 400.0 400 400.0 260 120 165 600 850 850 850 1300 1300 1300 1700 1700
Platinum resistance thermometer Pt100 JPt100 K J T
Thermocouple E L U N R S B W
2300 1800
Infrared temperature sensor PL II
10 to 70C 60 to 120 C 115 to 165 C 140 to 260 C
Analog input 0 to 50 mV
Temperature range (C)
Usable in the following ranges by scaling: -1999 to 9999 or -199.9 to 999.9
Setting number
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
24
25
19
20
21
22
23
Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
Models with Analog Inputs
Input type Input specification Setting range Setting number Current 4 to 20mA 0 to 20 mA 1 to 5 V Voltage 0 to 5 V 0 to 10 V
Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 0 1 2 3 4
Shaded settings are the default settings.
7
E5AN/E5EN
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). Alarm output operation Set value 0 1 *1 2 3 4 *1 5 *1 6 7 8 9 10 11 12 13 Alarm type Alarm function OFF Upper- and lower-limit Upper-limit Lower-limit Upper- and lower-limit range Upper- and lower-limit with standby sequence Upper-limit with standby sequence Lower-limit with standby sequence Absolute-value upper-limit Absolute-value lower-limit Absolute-value upper-limit with standby sequence Absolute-value lower-limit with standby sequence LBA (alarm 1 type only) PV change rate alarm When alarm value When alarm value X is positive X is negative Output OFF
ON OFF ON OFF ON OFF L SP X SP X SP L SP L SP H H H
Description of function No alarm
*2
ON OFF ON OFF X SP X SP
Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). Set the upward deviation in the set point by setting the alarm value (X). Set the downward deviation in the set point by setting the alarm value (X). Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). A standby sequence is added to the upper- and lower-limit alarm (1). *6
X SP X SP X 0 X 0 X 0 X 0
ON OFF
*3 *4
ON OFF
*5
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
X SP X SP X 0 X 0 X 0 X 0
ON OFF ON OFF
A standby sequence is added to the upper-limit alarm (2). *6 A standby sequence is added to the lower-limit alarm (3). *6 The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point. The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. A standby sequence is added to the absolute-value upper-limit alarm (8). *6 A standby sequence is added to the absolute-value lower-limit alarm (9). *6 *7 *8
ON OFF
ON OFF ON OFF
ON OFF
-----
*1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as "L" and "H." *2. Set value: 1, Upper- and lower-limit alarm
Case 1 Case 2 Case 3 (Always ON)
H < 0, L < 0 L H SP SP L H H > 0, L < 0 H > L H H SP L SP SP H L L H < 0, L > 0 H L H > 0, L < 0 H L H < 0, L > 0 H < L
*3. Set value: 4, Upper- and lower-limit range
Case 1 Case 2 Case 3 (Always OFF)
*5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the operation of the standby sequence. *7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the loop burnout alarm (LBA). *8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the PV change rate alarm.
H < 0, L < 0 L H SP SP L H H H SP L SP SP H L L H < 0, L > 0 H L H > 0, L < 0 H L H < 0, L > 0 H < L H > 0, L < 0 H > L
*4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above * Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. * Case 3: Always OFF
8
E5AN/E5EN
Characteristics
Indication accuracy Thermocouple: (0.3% of indicated value or 1C, whichever is greater) 1 digit max. *1 Platinum resistance thermometer: (0.2% of indicated value or 0.8C, whichever is greater) 1 digit max. Analog input: 0.2% FS 1 digit max. CT input: 5% FS 1 digit max. Thermocouple input (R, S, B, W, PL II): (1% of PV or 10C, whichever is greater) 1 digit max. Other thermocouple input: (1% of PV or 4C, whichever is greater) 1 digit max. *3 Platinum resistance thermometer: (1% of PV or 2C, whichever is greater) 1 digit max. Analog input: (1%FS) 1 digit max. 250 ms Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4 Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS) Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4 Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS) 0 to 3999 s (in units of 1 s) 0 to 3999 s (in units of 1 s) *5 0.5, 1 to 99 s (in units of 1 s) 0.0 to 100.0% (in units of 0.1%) -1999 to 9999 (decimal point position depends on input type) Thermocouple: 0.1C/ max. (100 max.) Platinum resistance thermometer: 0.1C/ max. (10 max.) 20 M min. (at 500 VDC) 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions 100 m/s2, 3 times each in X, Y, and Z directions 300 m/s2, 3 times each in X, Y, and Z directions Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g Front panel: IP66, Rear case: IP20, Terminals: IP00 Non-volatile memory (number of writes: 1,000,000 times) CX-Thermo version 4.0 or higher Provided on the bottom of the E5AN and E5EN. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN and E5EN *6 UL 61010-1, CSA C22.2 No. 1010-1 EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *7
Transfer output accuracy 0.3% FS max. Influence of temperature *2 Influence of voltage *2 Input sampling period Hysteresis
Proportional band (P) Integral time (I) Derivative time (D) Control period Manual reset value Alarm setting range Affect of signal source resistance Insulation resistance Dielectric strength Vibration resistance Destruction Shock resistance Destruction Weight E5AN E5EN Malfunction Malfunction
Degree of protection Memory protection Setup Tool Setup Tool port Approved standards Conformed standards
Standards
EMI: EN 61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 EMC Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11 *1. The indication accuracy of K thermocouples in the -200 to 1300C range, T and N thermocouples at a temperature of -100C max., and U and L thermocouples at any temperatures is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800C range is 3C max. The indication accuracy of the R and S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is 0.3 of PV or 3C, whichever is greater, 1 digit max. The indication accuracy of PL II thermocouples is 0.3 of PV or 2C, whichever is greater, 1 digit max. *2. Ambient temperature: -10C to 23C to 55, Voltage range: -15% to 10% of rated voltage *3. K thermocouple at -100C max.: 10C max. *4. "EU" stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is C or F. *5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s). *6. External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time. *7. Refer to information on maritime standards in Safety Precautions for E5@N/E5@N-H for compliance with Lloyd's Standards.
9
E5AN/E5EN
USB-Serial Conversion Cable
Applicable OS Applicable software Applicable models USB interface standard DTE speed Connector specifications Power supply Power supply voltage Current consumption Ambient operating temperature Windows 2000, XP, or Vista CX-Thermo version 4 or higher E5AN/E5EN/E5CN/E5CN-U/E5ANH/E5EN-H/E5CN-H/E5GN Conforms to USB Specification 1.1. 38400 bps Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) Bus power (Supplied from USB host controller.) 5 VDC 70 mA 0 to 55C (with no condensation or icing) Maximum heater current Input current indication accuracy Heater burnout alarm setting range *1 SSR failure alarm setting range *2 -20 to 60C (with no condensation or icing) 10% to 80% 2,000 m max. CT input (for heater current detection)
Current Transformer (Order Separately) Ratings
Dielectric strength 1,000 VAC for 1 min E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Armatures (2) Plugs (2) Vibration resistance 50 Hz, 98 m/s2 Weight Accessories (E54-CT3 only)
Heater Burnout Alarms, SSR Failure Alarms, and Heater Overcurrent Alarms
Models with detection for singlephase heaters: One input Models with detection for singlephase or three-phase heaters: Two inputs 50 A AC 5% FS 1 digit max. 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms
Ambient operating humidity 10% to 80% Storage temperature Storage humidity Altitude
Weight Approx. 100 g Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable.
Communications Specifications
Transmission line connection method Communications RS-485: Multipoint RS-232C: Point-to-point RS-485 (two-wire, half duplex) or RS232C CompoWay/F, SYSWAY, or Modbus 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps ASCII 7 or 8 bits 1 or 2 bits Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus None RS-485, RS-232C None 217 bytes
Synchronization method Start-stop synchronization Protocol Baud rate Transmission code Data bit length * Stop bit length *
Heater overcurrent alarm 0.1 to 49.9 A (in units of 0.1 A) setting range *3 Minimum detection ON time: 100 ms *1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3. For heater overcurrent alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value).
Electrical Life Expectancy Curve for Relays (Reference Values)
Life ( x 104 operations) 500 300
Error detection
100 50 30
Flow control Interface Retry function Communications buffer
E5AN/E5EN 250 VAC, 30 VDC (resistive load) cos = 1
10 5 3
Communications 0 to 99 ms response wait time Default: 20 ms * The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level.
1 0 1 2 3 4 5 6 Switching current (A)
Note: Do not connect a DC load to a Controller with a Long-life Relay Output.
10
E5AN/E5EN
External Connections
* A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current. The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit. * Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.
Controllers
* 100 to 240 VAC * 24 VAC/VDC (no polarity) Control output 1
Relay output 250 VAC, 5A (resistive load) Voltage output (for driving SSR) 12 VDC, 40 mA Current output 0 to 20 mA DC 4 to 20 mA DC Load: 600 max.
The E5@N-@@@T@ is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
Event Inputs EV2 EV1 CT1/CT2 Control Output 2
CT 1
Option Units
Communications E53-EN01 RS-232C SD 11 12 RD 13 SG E53-EN03 RS-485 B (+) 11 12 A (-)
13
E53-AKB Event inputs
11 12 13
EV2 EV CT1/CT2
1
11 12 13 14
Input power supply
2 3
DO NOT USE
Control output 1
4 5
External Power Supply
Control output 2
DO NOT USE
15
CT 2
Auxiliary output 3
External power supply 12 VDC, 20 mA
DO NOT USE DO NOT USE V
Control output 2 Voltage output (for driving SSR)
12 VDC, 21 mA
6 7
16 17 18 19 20
DO NOT USE DO NOT USE A B B TC/Pt universal-input
Auxiliary output 2
8 9
Long-life relay output 250 VAC, 3 A (resistive load)
mA
Auxiliary output 1
10
DO NOT USE Analog input
A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned.
Auxiliary output 1, 2, 3
Relay outputs
250 VAC, 3 A
(resistive load)
11
E5AN/E5EN
Nomenclature
E5AN
Temperature unit
E5EN
Operation indicators
SUB1 SUB2
PV
No.1 display Temperature unit
SUB1 SUB2 HA SUB3
Operation indicators
SUB3 HA
PV
No.1 display
SV
OUT1 OUT2 STOP CMW MANU
No. 2 display
OUT1 STOP OUT2 CMW MANU
SV
No.2 display No.3 display
MV
No. 3 display
Operation indicators
MV
Programmable Function Key/ Auto/Manual Key
PF
A/M
Mode Key Up Key Level Key
Up Key Programmable Function Key/ Auto/Manual Key
PF
A/M
E5AN
Down Key
E5EN
Level Key
Mode Key
Down Key
* A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level, refer to the User's Manual, Basic Type (Cat. No. H156).
Dimensions
E5AN
(Unit: mm)
Mounted Separately
92 6 2 79.2
+0.8 0
Group Mounted
(96 x number of units - 3.5)
+1.0 0
92
+0.8 0
96 x 96
112
91
120 min.
Group mounting does not allow waterproofing.
92 Terminal Cover (E53-COV16) (Accessory) Crimp terminal size: M3.5
+0.8 0
Waterproof Packing (Accessory)
Mounting Bracket (Accessory)
* Recommended panel thickness is 1 to 8 mm. * Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) * To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. * When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
12
E5AN/E5EN
E5EN
6 48 2 79.2
Mounted Separately
+0.6 45 0
Group Mounted
(48 x number of units - 2.5)
+1.0 0
92
+0.8 0
96
112
91 120 min. Group mounting does not allow waterproofing.
92 Waterproof Packing (Accessory) Mounting Bracket (Accessory) Terminal Cover (E53-COV16) (Accessory) Crimp terminal size: M3.5
+0.8 0
* Recommended panel thickness is 1 to 8 mm. * Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) * To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. * When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
Accessories (Order Separately)
USB-Serial Conversion Cable
E58-CIFQ1
(2,100) 250 LED (SD) 1,765
USB connector (type A plug)
LED (RD)
Serial connector
Terminal Covers
E53-COV16 (Six Covers provided.)
1.2 3.2
10
44.8
13
E5AN/E5EN
Waterproof Packing
Y92S-P4 (for DIN 96 x 96) Y92S-P5 (for DIN 48 x 96)
Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required.
Current Transformers
E54-CT1
21 15 5.8 dia. 7.5 2.8
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 4002 Winding resistance: 182
Output voltage (Eo) V (r.m.s.) 100 V 10 50 Hz
25
3 10.5 40 Two, 3.5 dia. 10 30
1 k
Distortion factor 10% 3% 1%
1
100 mV 100 RL = 10
10
E54-CT3
2.36 dia. 30 12 dia. 9
1 100 V 10 1
10
100 mA
1
10
100 1,000 A
40 x 40
Thru-current (Io) A (r.m.s.)
Two, M3 (depth: 4)
E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Temperature Controller is 50 A.) Number of windings: 4002 Winding resistance: 80.8
Output voltage (Eo) V (r.m.s.) 100 V 10 50 Hz 1 k 500
15
30
E54-CT3 Accessory
* Armature
Approx. 3 dia.
Connection Example
Armature Plug Lead
1
Distortion factor 10% 3% 1%
100 mV 100 50 RL = 10 1 100 V 10 1
18
10
* Plug
Approx. 6 dia.
(22)
10
100 mA
1
10
100 1,000 A
Thru-current (Io) A (r.m.s.)
14
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: * Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. * Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. * Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
2009.11 In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
http://www.ia.omron.com/
OMRON Corporation
(c)Copyright OMRON Corporation 2009 All Right Reserved.


▲Up To Search▲   

 
Price & Availability of E5AN-R3HML-500-N

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X