Celab
Specification Input Voltage Input Frequency
Telephony 750 Watts Uninterruptible Power Supply
230VAC, +15% - 10% Single Phase 47 to 63Hz EMC meets requirement of EN50081-1 & EN50082-1 15A Typical 54V to 58V (adjustable by potentiometer) 0-10A at 56V Load +/- 1%, Line +/- 0.2% In battery mode the output will be equal to the battery voltage, less 0.5V 100mV peak to peak, up to 20 MHz 4A DC >85% at full load -20C to +65C 0.02% per C
Emissions/Immunity Standards Inrush Current Output Voltage Output Current Range Output Regulation Integrated battery management system. Designed for street cabinet applications. Non latching thermal protection. 10A output with separate 4A charging facility. Output voltage adjustable from 54V to 58V DC. Automatic and remote controlled battery condition testing. Comprehensive range of management alarms.
Output Noise & Ripple Battery Charging Current Efficiency Operating Temperature Temperature Coefficient
Protective Features If ambient temperature exceeds 65C the power supply is protected by a non-latching thermal cut-out. Insulation - Input to Chassis 1500Vrms Insulation - Output to Chassis Insulation - Input to Output 3750Vrms Insulation - Output to Output Safety Standards Meets BSEN60950, LVD Compliant, CE marked. Current Limit Trip and restart, 20A +/- 1A Overvoltage Protection Low Battery Disconnect Auto Battery Test Feature
100Vrms 100Vrms
Trip and restart, 64V +/- 1V 42.5V +/- 0.5V The power supply will automatically load check the battery condition approximately every 20 days (or longer if required) for approximately 20 minutes to establish that the battery is `good'. If the battery voltage is below 47 volts, alarm 4 will operate.
Alarms The following 6 alarms are isolated and have a pair of contacts that can be factory configured open or closed in normal operation. Alarm 1: Input Mains Good Alarm 2: Output Voltage Good Alarm 3: Power Supply Good Alarm 4: Battery Good Alarm 5: Alarms 1 to 4 in Series Alarm 6: Thermal Cut Out Alarm Indicators Alarms 1 to 4 - Four Green LED's Output Current Indicator LED display of total output current (including battery charging current) in 2A increments to 16A. Mechanical Specification Mains Input Size Weight Specification Note:
IEC 320 connector with 10A fusing 19" rack x 2U high x 240mm deep 6kg For any requirements not specified above, please contact the sales department.
The SP1470 series has been specifically designed to reliably withstand the very high and low temperatures experienced in street cabinets. The battery management system enhances the life of the batteries by controlling the charging current and avoiding deep discharge. Regular battery test loading monitors battery health without risk of system failure.
Murata Power Solutions (Celab) Ltd, 25 Woolmer Way, Bordon, Hampshire, GU35 9QE
Tel: +44 (0) 1420 477011
Fax: +44 (0)1420 487476
www.murata-ps.com/celab


▲Up To Search▲   

 
Price & Availability of SP1470

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X